Industrial Switches

Abb Industrial Thermomagnetic Θερμομαγνητικός Διακόπτης 4,0-6,3A 50kA 17935

Key features:

  • Type: Switch
  • Category: Thermomagnetic
See full description
31 40 €
Delivery by Tue, 01 Dec
3,50 €  
Do you want it with Free shipping?
From Ilektrapothiki THessalonikis AE
Θεσσαλονίκη, Θεσσαλονίκης
In-store pickup available
2 pieces
See Industrial Materials on the page of Ilektrapothiki THessalonikis AE
What if it breaks?

You're covered by the statutory 2-year warranty. Contact us and we'll handle the entire process with the store, ensuring your issue is resolved with prompt support through a repair, replacement, or refund.

What if I change my mind?

No problem, as long as it's within 14 days. We'll come pick it up or you can choose the Skroutz Point that suits you, completely free for up to 2 times per year, and we'll refund your money. Get Skroutz Plus to enjoy unlimited free returns.

Description

Description

The ABB MS116-6.3 thermal-magnetic circuit breaker is used to switch motors on and off, and to protect them against short circuits, overloads and phase failures, without a fuse. The motor’s rated current is set using the selector on the device. It is suitable for single-phase and three-phase applications.

  • Current setting range: 4.0–6.3 A
  • Rated operating current: 6.3 A
  • Instantaneous short-circuit current setting: 78.8 A
  • Rated operational voltage: 690 V AC
  • Rated insulation voltage: 690 V
  • Rated impulse withstand voltage: 6 kV
  • Short-circuit breaking capacity Ics: 50 kA at 230 V AC and 400 V AC, 6 kA at 440 V AC and 500 V AC, 2 kA at 690 V AC
  • Ultimate short-circuit breaking capacity Icu: 75 kA at 230 V AC and 400 V AC, 18 kA at 440 V AC, 15 kA at 500 V AC, 3 kA at 690 V AC
  • Trip class: 10A
  • Rated operating power AC-3: 2.2 kW at 400 V, three-phase
  • Poles: 3
  • Electrical endurance: 100,000 cycles
  • Mechanical endurance: 100,000 cycles

Manufacturer

See full description
Questions

Questions

Do you have a question about the product?

3 users have this product and can help you

Ask for the product

Description

The ABB MS116-6.3 thermal-magnetic circuit breaker is used to switch motors on and off, and to protect them against short circuits, overloads and phase failures, without a fuse. The motor’s rated current is set using the selector on the device. It is suitable for single-phase and three-phase applications.

  • Current setting range: 4.0–6.3 A
  • Rated operating current: 6.3 A
  • Instantaneous short-circuit current setting: 78.8 A
  • Rated operational voltage: 690 V AC
  • Rated insulation voltage: 690 V
  • Rated impulse withstand voltage: 6 kV
  • Short-circuit breaking capacity Ics: 50 kA at 230 V AC and 400 V AC, 6 kA at 440 V AC and 500 V AC, 2 kA at 690 V AC
  • Ultimate short-circuit breaking capacity Icu: 75 kA at 230 V AC and 400 V AC, 18 kA at 440 V AC, 15 kA at 500 V AC, 3 kA at 690 V AC
  • Trip class: 10A
  • Rated operating power AC-3: 2.2 kW at 400 V, three-phase
  • Poles: 3
  • Electrical endurance: 100,000 cycles
  • Mechanical endurance: 100,000 cycles

Manufacturer

Abb - Industrial Switches Abb
31,40 €
3,50 €