Switch disconnector 1-0-2 1P 16A surface mounted - ŁK16R-1.834P03
Technical Specifications:
- Rated insulation voltage Ui: 690V
- Rated impulse withstand voltage Uimp: 6 kV
- Rated continuous current Iu=Ith: 16A
- Rated operational power Pe in category AC-3: 5 kW (230 V), 8 kW (400 V), 10 kW (500 V), 11 kW (690 V)
- Rated operational power Pe in category AC-4: 5 kW (230 V), 7 kW (400 V), 7 kW (500 V), 6 kW (690 V)
- Rated operational current in category AC-3: 16A (230V), 16A (400V), 16A (500V), 12A (690V)
- Rated operational current in category AC-4: 16A (230V), 13A (400V), 10A (500V), 7A (690V)
- Rated operational current in category DC-1: 8A (110V), 2.5A (220V)
- Rated operational current in category DC-21: 10A (110V), 3A (220V)
- Short-time current withstand rating Icw(1s): 0.9 kA
- Rated short-circuit current Icm: 1.3 kA
- Rated conventional short-circuit current: 13 kA
- Rated current of gG fuse connection: 16A
- Mechanical endurance: 3.0 million switching cycles
- Ambient temperature: -40 ... +70°C (operation), -40 ... +70°C (storage)
- Connection cable cross-section: 1.5...4 mm²
- Protection degree: IP65
- Shock resistance: 2...13, 2...100 Hz ± 1 mm ± 0.7 g
- Surge withstand: 15 g, 11 ms
- Resistance to thermal cycles: 55°C, 95% relative humidity
- Resistance to cyclic salt mist: test accuracy 1
Specifications
- Number of Poles
- 1
- Nominal Voltage
- 230 V
- Rated Voltage
- 16 A
Features & Functions
- WiFi
- No
Important information
Specifications are collected from official manufacturer websites. Please verify the specifications before proceeding with your final purchase. If you notice any problem you can report it here.