Overload relay, 80...104A, class 10A (LRD4365)
Technical specifications:
- Product compliance: LC1D115, LC1D150
- Network type: AC/DC
- Trip category for overload: category 10A according to IEC 60947-4-1
- Thermal protection adjustment range: 80...104A
- Nominal insulation voltage: power circuit 1000V according to IEC 60947-4-1
- Power circuit 600V according to CSA
- Power circuit 600V according to UL
- Network frequency: 0...400Hz
- Mounting assistance: plate with specific components, rail with specific components, under the contactor
- Activation threshold: 1.14 +/- 0.06 Ir according to IEC 60947-4-1
- Rated thermal current: 5A for signaling circuit
- Permissible current: 0.06A at 440V DC-13 for the signaling circuit
- 0.12A at 600V AC-15 for the signaling circuit
- Operating voltage rating: 690V AC 0...400Hz
- Nominal surge withstand voltage: 6kV
- Phase loss sensitivity: activation current 130% of the Ir value in two phases
- The last at 0
- Control type: red STOP button, blue button for RESET operation
- Temperature compensation: -20...60°C
- Fire resistance: 850°C according to IEC 60695-2-1
- Protection level: IP20