Water Switch & Valves

Giacomini Differential Valve R147ny004 3/4 Inch Internal Thread HVAC Installation Bypass Brass

The Giacomini R147NY004 differential pressure valve is designed for use in heating and cooling hydronic systems, such as radiator installations, fan coil units, or radiant systems. In these setups,...
The Giacomini R147NY004 differential pressure valve is designed for use in heating and cooling hydronic systems, such as radiator installations, fan coil units, or radiant systems. In these setups, all circuits can close simultaneously, which may lead to increased upstream pressure of the pump. Without a differential pressure valve, this overpressure can...
See Description & Specifications See Description & Specifications
32 84 €
33 Coins 33 Coins
Delivery by Tue, 13 Oct
2,50 € to a Skroutz Point
or   3,50 €   shipping cost
Sent from Romania
From Bricoo
Romania
16 pieces
See Hydraulic Equipment on the page of Bricoo
What if I want to return it?

You can return it for free within 14 days. We will come to your place, return it for free, and you will get your money back.

Questions

Description & Specifications

The Giacomini R147NY004 differential pressure valve is designed for use in heating and cooling hydronic systems, such as radiator installations, fan coil units, or radiant systems. In these setups, all circuits can close simultaneously, which may lead to increased upstream pressure of the pump. Without a differential pressure valve, this overpressure can cause noise in the system and even damage to the pump. The R147NY004 valve maintains a stable pressure in the system regardless of flow changes, automatically releasing excess pressure between the supply and return pipes. This ensures quiet and safe system operation, extending the lifespan of the pump and other components. The device features a scale from 1 to 6 meters of water column, allowing precise adjustment of the desired setting simply by turning the handle. During operation, the valve can release flows up to 1000 l/h, while for higher flows, installing multiple valves in parallel is recommended. The installation can be performed horizontally or vertically, following the flow direction marked on the valve body. It is always installed between the supply and return pipes, immediately after the pump. Constructed from durable CW617N brass, with a stainless steel spring and EPDM seals, it guarantees resistance to pressure, high temperatures, and corrosion.
  • Type: differential pressure valve (by-pass)
  • Application: heating and cooling systems (HVAC)
  • Connections: G 3/4” F x G 3/4” F
  • Working fluid: water, aqueous solutions (max. 50%)
  • Maximum working temperature: 120 °C
  • Maximum working pressure: 10 bar
  • Maximum differential pressure: 60 kPa
  • Adjustment range: 1 – 6 m.w.c.
  • Maximum bypass flow: 1000 l/h
  • Body: CW617N brass UNI EN 12165
  • Spring: stainless steel AISI 302
  • Seals: EPDM
  • Handle: ABS
  • Installation: horizontal or vertical
  • Dimensions: length 91–108 mm, height 67–84 mm, width 54 mm
Main features:
  • Range of adjustment width, allowing installation in systems with different capacities.
  • Additional 1/4” connection for mounting an automatic air vent (sold separately), which allows periodic removal of gases accumulated in the valve, preventing malfunctions.
  • Can release flows up to 1000 l/h; for higher flows, installing multiple valves in parallel is recommended.
Advantages:
  • Maintains steady pressure in the system regardless of flow variations.
  • Protects the pump and other components from overpressure.
  • Reduces network noise caused by high water velocity.
  • Simple and precise setting via scale.
  • Durable construction from corrosion-resistant brass.
  • Can be installed horizontally or vertically.
  • Compatible with water and aqueous solutions up to 50%.
Installation: The R147N valve must always be installed after the pump, between the supply and return pipes. It can be installed horizontally or vertically, following the flow direction indicated on the valve body. It can be used as a standalone component (e.g., in the technical room or distribution boxes of the system) or integrated into pre-assembled boiler groups or manifolds for radiant systems. Adjustment (Calibration): The valve is adjusted by turning the scale. The scale, ranging from 1 to 6 meters of water column, allows setting the desired differential pressure value.