The Schneider Electric iC60N miniature circuit breaker is designed for distribution applications and protects two poles. It uses thermal-magnetic tripping with a D curve and operates in AC and DC networks.
- Type: Miniature circuit breaker
- Range: Acti 9
- Poles: 2
- Rated current: 1 A
- Tripping: Thermal-magnetic, D curve
- Breaking capacity: 6 kA at 400 V AC, 50/60 Hz, in accordance with EN 60898-1 and IEC 60898-1
- Isolation function: Yes
- Network frequency: 50/60 Hz
- Magnetic tripping threshold: 12 x In +/- 20%
- Utilization category: A
- Limitation class: 3
- Rated insulation voltage: 500 V AC, 50/60 Hz
- Rated impulse withstand voltage: 6 kV
- Operation: Toggle
- Indication: Contact position and tripping
- Mounting: DIN rail
- Dimensions: 36 x 91 x 78.5 mm
- Weight: 0.25 kg
- Colour: White
- Mechanical endurance: 20,000 cycles
- Electrical endurance: 10,000 cycles
- Terminals: Dual, top or bottom
- Rigid conductor cross-section: 1...25 mm²
- Flexible conductor cross-section: 1...16 mm²
- Stripping length: 14 mm
- Tightening torque: 2 N·m
- Earth-leakage protection: With a separate block
- Degree of protection: IP20
- Pollution degree: 3
- Overvoltage category: IV
- Tropicalization: 2
- Relative humidity: 95% at 55 °C
- Operating temperature: -35...70 °C
- Storage temperature: -40...85 °C
- Standards: EN 60898-1, EN 60947-2, IEC 60898-1, IEC 60947-2
Specifications
- Number of Poles
- 2
- Rated Current
- 1 A
Power Supply
- AC
- Yes
- DC
- No
Important information
Specifications are collected from official manufacturer websites. Please verify the specifications before proceeding with your final purchase. If you notice any problem you can report it here.