Surge arrester B+C 4P 25kA with signalling PRD1 (16332)
- Product: Multi 9 PRD1
- Product Type: Surge arrester with plug-in cartridge
- Application: Distribution
- Number of poles: 3P + N
- Remote signalling: YES
- Total signal contacts: 1 SD (1 W/R)
- Type of surge protective device: Electrical power distribution network
- Grounding system: TN-S TT
- Type of surge protective device: 1 + 2
- Lightning strike protection technology: Spark gap MOV
- [Ue] rated operating voltage: 230 V (+/- 10 %) AC 50 Hz, 400 V (+/- 10 %) AC 50 Hz
- Rated discharge current [In]: Common mode: 100 kA N/PE; Differential mode: 25 kA L/N
- [Iimp] impulse current: 100 kA Common mode: N/PE 50 A.s; 25 kA Differential mode: L/N 12.5 A.s
- [Uc] maximum continuous operating voltage: Common mode: 350V N/PE; Differential mode: 350V L/N
- Voltage protection level: 1.5 kV type 2 common mode N/PE; 1.5 kV type 2 differential mode L/N
- [If] forward: current 25 kA differential mode L/N, 0.1 kA common mode N/PE
- Disconnection device type: Relative protective switch for conductors NG125N 80 A Icu 10 kA curve C
- Combined circuit breaker: NG125N 80 A Icu 15 kA curve C, NG125N 80 A Icu 25 kA curve C
- Combined fuse: 315 A gG according to STANDARD
- Local signalling: Indicator color: White/Red
- Signalling circuit voltage: AC 250V 50/60Hz
- Output signal current: 1A
- Mounting method: Snap-in
- Mounting method: DIN rail 9 mm
- Dimensions: Height 90 mm, Width 142.8 mm, Depth 70 mm
- Product weight: 1.43 kg
- Color: Anthracite grey (RAL 7016)
- Material: PBT (polybutylene terephthalate)
- Product Number
- 16332
- Number of Poles
- 4
- Type
- T2
- Replacement Cartridge
- No
- Maximum Discharge Current (kA)
- 25